Set the range and alarm action by the hazard in each area
The same gas can need a different range and a different alarm action in different parts of one site, because the risk is different. Where people work, the concern is exposure, so the range has to resolve low concentrations. Where gas can build up near ignition sources, the concern is a flammable mixture, so the measurement is in %LEL and the alarm drives ventilation or shutdown.
Field example: ammonia on refrigerated fishing vessels
Each vessel in the batch had five freezer holds and a compressor space to watch, with fans and a sprinkler system to be switched on alarm. The customer's specification asked for 0–1000 ppm ammonia everywhere. Eranntex engineers split it by risk. The freezer holds were set to 0–100 ppm, because the danger there is exposure of the crew who enter them. The compressor space was set to 0–100 %LEL, because a large release there is a fire and explosion risk, and its low alarm at 20 %LEL starts the sprinklers through a relay on the controller. Each vessel received single-gas ammonia detectors on RS485 and one MIC3000, whose eight standard relays covered the fans, sprinklers and beacons. The shipyard's contractor installed the system with remote guidance from Eranntex.
The 20 %LEL setting belongs to that project. Alarm levels on another site follow its own hazard assessment and the rules that apply there.
Mounting height: where the gas will actually collect
Detector height follows where the released gas will go: low for gases heavier than air, high for gases lighter than air, and close to the release source for gases near the density of air. That starting point then has to be corrected for how the gas is released and how air moves on the site. No single height applies everywhere, and the figure that governs a project is the one in the rules adopted where it is built.
IEC 60079-29-2, the international standard on selecting, installing, using and maintaining flammable gas detectors, states placement as principles and gives no mounting heights. China's petrochemical design standard GB/T 50493-2019 does give heights, and it ties them to four density classes, judged by the ratio of the gas's molecular weight to that of air (clause 4.1.2). Its clause 6.1.2 recommends (the standard says 宜, "should preferably", not a mandatory "shall"):
| GB/T 50493-2019 class | Molecular-weight ratio to air | Recommended detector position (cl. 6.1.2) | Examples (ratio, calculated) |
|---|---|---|---|
| Heavier than air | ≥ 1.2 | 0.3–0.6 m above ground or floor | Propane (1.52), chlorine (2.45) |
| Slightly heavier | ≥ 1.0 and < 1.2 | 0.5–1.0 m below the release source | Hydrogen sulfide (1.18) |
| Slightly lighter | 0.8–1.0 | 0.5–1.0 m above the release source | Carbon monoxide (0.97) |
| Lighter than air | ≤ 0.8 | Within 2.0 m above the release source | Methane (0.55), ammonia (0.59), hydrogen (0.07) |
Hydrogen sulfide is heavier than air, but its ratio of 1.18 puts it in the slightly-heavier class, so this standard recommends a position below the release source rather than a fixed height off the floor. The same standard places ambient oxygen detectors 1.5–2.0 m above the floor (clause 6.1.3), puts detection points around release sources such as compressor and pump seals, sampling points, drains and vents, and frequently opened flanges (clause 4.1.3), and keeps at least 0.5 m of clearance between a detector and the surrounding pipework or equipment (clause 6.1.1).
Manufacturer guidance sits apart from these rules. One US detector manufacturer gives 15–30 cm from the ground for heavier-than-air gases and the breathing zone, 1.2–1.8 m, for gases near the density of air such as carbon monoxide, and tells installers to follow local codes and the authority having jurisdiction. Its 15–30 cm is lower than the 0.3–0.6 m in GB/T 50493-2019; the two are different sources, not one requirement.
On a real site, release conditions and air movement shift all of these positions. A gas that is heavier than air can still rise at first if it is released hot or under pressure. A leak from an elevated flange can pass a detector mounted low. Ventilation, doors, extract fans and air supply diffusers move gas away from where density alone would put it, so detectors are not mounted next to fans or openings to the outdoors. The oil and gas page covers a site where methane and hydrogen sulfide need detectors at two heights.
When you send a layout, mark the release sources, the low points, the ventilation and the standard adopted for the project, so detector positions can be checked against the gas and the actual conditions rather than against a generic height.
How many controllers, and where they go
Controllers are usually counted by area, not by dividing the total number of detectors by one controller's capacity. A controller sits where someone will see and act on its alarm, and its relays switch the equipment in that area.
On one chemical-plant project, the tender asked for 98 flameproof CO detectors (0–100 ppm) and 16 explosion-protected controllers. The enquiry specified 4–20 mA. After working through how 16 controllers would take 98 detectors, the system was built on RS485 with MIC2000-Ex controllers, each serving the detectors in its own area: most served a dozen or so, some a single detector. None came close to its 128-input limit.
Where the controller is mounted is the next decision. The MIC-1000-Ex and MIC2000-Ex are explosion-protected and designed to sit in the hazardous area itself, for example on a skid or tank farm with no control room. Where a safe-area control room exists, Eranntex recommends a standard controller there: it costs less, and opening it for adjustment does not need a hazardous-area work permit.
Who has to react also decides where the signal goes. Eranntex supports four arrangements:
- detectors to a MIC controller that drives local beacons, fans or valves;
- detectors to a MIC controller that also passes data to a DCS or plant network over RS485 Modbus, or over optional 4–20 mA, Ethernet or wireless outputs;
- detectors straight to a DCS, with no Eranntex controller;
- a mix of the two.
Every MIC controller sets low and high alarm limits separately for each channel, has three alarm levels, and can link each channel to up to three programmable relays, so one detector can start a fan at the first level and close a valve at the second. Each detector also has its own dry-contact relays (up to two on the MIC-500S models and MIC-600-CB, up to three on the GTYQ-MIC-600), which can switch a local beacon even where the signal goes straight to a DCS.
Cable routes, distance and uplink
Where cable can be pulled, RS485 usually saves the most. On 4–20 mA, a multi-gas detector needs one analog loop per gas. On RS485, one bus pair carries every gas from many detectors. Eranntex engineers usually wire an RS485 detector with one four-core cable, two cores for the 24 V DC supply and two for the RS485 pair, so each run is pulled once. On a multi-building university laboratory project with several hundred detection points, this replaced the integrator's first plan of two separate two-core cables.
Electrical loading limits one RS485 bus to about 32–64 detectors in Eranntex practice. Larger systems use more bus loops on the controller, or RS485 repeaters and hubs. Each detector needs a unique address from 1 to 128 and the same baud rate as the controller. Send a tag list with the order and Eranntex sets the addresses at the factory.
Distance sets whether the controller can power the detectors. The MIC-1000 is specified at 2.5 W per input and can power all 32 analog detectors from its internal supply. A separate 24 V DC supply near the detectors is worth adding when cable runs go beyond roughly 300–500 m, when many detectors share one RS485 bus, or when the system has to run for a long time after a mains failure.
Without a cable run, the link changes. In one tunnel project, each tunnel had two multi-gas detectors and a MIC3000 at the portal, linked by network bridges, a pair at each bend, instead of cable. The bridges the customer bought had no RS485 port, so Eranntex fitted a small TCP/IP module inside each detector. On site the signal proved weaker than planned and more bridges were added. The bridges were not explosion-protected, and Eranntex told the customer so, since that is a decision for the site's explosion-protection design.
The uplink each area needs can narrow the controller choice. On the laboratory project, some buildings needed a network (TCP/IP) uplink and others a cellular (GPRS) link. Only the MIC3000 offers both in one controller, so the project used different controller versions by location.
Hazardous-area interface
When detectors sit in a hazardous area and the controller in a safe area, Eranntex generally recommends a safety barrier or isolating barrier on the safe-area side of each detector circuit, sized by its engineers from the area classification and the detector model before shipment. Whether it is fitted is decided by the site's explosion-protection design. The detector's certificate states its protection type: the GTYQ-MIC-500S family is flameproof (Ex db IIC T6 Gb), and the GTYQ-MIC-600 is certified Ex da ia IIC T6 Ga under CE24.5822X, whose annex includes intrinsic-safety parameters for its RS485 circuit.
Environment and sensor life
Heat, humidity, condensation, washdown, corrosive gases and dust all affect sensors and enclosures, and the right measures depend on the actual site. In the tunnel project, ambient temperature was high, and long exposure to high temperature shortens sensor life. That affects the sensor replacement plan and running cost as well as the detector choice.
Eranntex works out environmental measures, such as protective accessories, sampling arrangements and sensor replacement intervals, project by project. Describe the conditions at each point in your enquiry: normal and peak temperature, humidity and condensation, whether the area is hosed down, and any corrosive or dusty atmosphere.
Plan for mains failure
Decide how long the system has to keep alarming without mains power, and who provides that time. The MIC-1000 has a 12 V DC, 7 Ah backup battery as standard; on the MIC-1000-Ex, MIC2000-Ex and MIC3000 a 24 V DC, 5 Ah backup battery is optional. On the fishing vessels, backup was left to the ships' own UPS because the required hold time had not been defined. If your site needs hours of operation after a power cut, say so at the start, because it changes the power design.
Reference: counting channels and choosing the signal
These rules apply once the site questions above are answered.
Count channels per gas, not per detector. Eranntex controllers are sized in gas channels, so a four-gas detector uses four channels whichever way it is wired. On 4–20 mA it needs four analog inputs and is ordered with four analog output channels; on RS485 it uses one pair of wires and one Modbus address, and the controller still manages four channels. Six four-gas detectors make 24 channels: on 4–20 mA only the MIC-1000 and MIC3000 have that many analog inputs, while on RS485 they fit within any of the four MIC controllers.
| Aspect | 4–20 mA | RS485 Modbus RTU |
|---|---|---|
| Wires per detector | One loop per gas | One shared bus pair for many detectors |
| What it carries | Live concentration over the 0–100% range; fault and over-range shown as defined currents below 4 mA or above 20 mA | Live concentration, low and high alarm states and fault state for every gas |
| Where alarm limits sit | Usually in the DCS, or in the controller's relay logic | In the detector and controller; the DCS reads the states |
| Typical use | Direct input to a DCS or PLC analog card | Many points on one cable to a MIC controller, or to a DCS over Modbus |
All five Eranntex fixed detectors provide three-wire 4–20 mA and RS485 Modbus RTU as standard, and all four MIC controllers accept both at the same time. The fault and over-range currents are one factory-default set across the range, given in the technical documents and changeable at order to match a DCS input configuration; a broken loop is different, because the current falls to near zero. Eranntex supplies the Modbus register map for the specific model with the shipment, or earlier on request when the DCS is being configured. HART is optional on all five detectors and is used with a DCS or handheld communicator; the MIC controllers do not take HART as an input.
| Controller | Mounting | 4–20 mA inputs | RS485 inputs | Relays (standard / optional) | Backup power |
|---|---|---|---|---|---|
| MIC-1000 | Wall, safe area | 1–8, 16, 24 or 32 | Up to 128 | 4 + 1 common / 8, 12, 16, 24 or 32 | 12 V DC, 7 Ah, standard |
| MIC-1000-Ex | Wall, explosion-protected | 1–8 | Up to 128 | 4 + 1 common / 8, 16, 24 or 32 | 24 V DC, 5 Ah, optional |
| MIC2000-Ex | Wall, explosion-protected | 1–8 | Up to 128 | 4 + 1 common / 8, 16, 24 or 32 | 24 V DC, 5 Ah, optional |
| MIC3000 | Wall, safe area, 9-inch touchscreen | 1–8, 16, 24 or 32 | Up to 256; cascaded systems up to 1000 input channels | 8 + 1 common / 16, 24 or 32 | 24 V DC, 5 Ah, optional |
Standard relay ratings are 3 A at 32 V DC or 3 A at 220 V AC on the MIC-1000, MIC-1000-Ex and MIC2000-Ex (common alarm output 12 A at 32 V DC or 7 A at 240 V AC), and 3 A at 250 V AC or 3 A at 30 V DC on the MIC3000 (common alarm output 10 A at 277 V AC or 12 A at 125 V AC). Relay assignment and ratings can be customized for a project. The 128 and 256 figures are the most channels one controller can manage; when a project mixes analog and RS485 inputs, Eranntex sets the allocation from the point list and pre-commissions the controller before shipment.
What to send with an enquiry
A site description lets Eranntex size the system once instead of revising it after the first quotation. For each detection point, and for the site as a whole, the useful information is:
Enquiry worksheet
Site and point list for a fixed gas detection system
| Tag or location | Gas | Why it is monitored (exposure or flammable risk) | Release source and where gas can collect | Mounting surface and height constraints | Temperature, humidity, washdown, corrosion or dust | Hazardous-area zone |
|---|---|---|---|---|---|---|