Confirmed technical specifications| Ingress protection | IP66 |
|---|
| Dimensions | 240 × 160 × 90 mm; 240 × 220 × 90 mm with alarm (L × W × H) |
|---|
| Weight | 1.4 kg — 1.6 kg with the audio-visual alarm. |
|---|
| Operating temperature | -40 °C to 70 °C |
|---|
| Display size | 2 in |
|---|
| Data storage | > 200,000 records |
|---|
| Alarm volume | > 105 dB — At 30 cm. |
|---|
| Sampling method | Diffusion |
|---|
- Standard gas configuration
- 1 gas
- Expanded gas configuration
- No higher gas-count expansion documented
- Sensor configuration
- Dual-beam infrared; documented service life 10 years
- Power supply
- 24 V DC; 220 V AC optional
- Signal output
- RS485 Modbus RTU and three-wire 4–20 mA standard; HART 5 or HART 7 optional
- Typical accuracy
- ±3% FS; higher-accuracy sensor option available
- Response time
- T90 ≤ 4 s
- Recovery time
- ≤ 5 s
- Operating humidity
- 10–95% RH
- Explosion protection
- Ex db IIC T6 Gb
- Enclosure option
- IP67 available as a custom configuration
- Local operation
- 4-key keypad, infrared remote control and magnetic-wand operation