Confirmed technical specifications| Ingress protection | IP66 |
|---|
| Weight | Approx. 2 kg |
|---|
| Operating temperature | -20 °C to 55 °C — Typical operating range. |
|---|
| Dimensions | 280 × 151 × 110 mm (L × W × H) |
|---|
- Sensor configuration
- 2 infrared sensors
- Detection distance
- 15–50 m depending on the target medium and test fire
- Response time
- 1–10 s depending on the target medium
- Field of view
- Infrared >90°
- Power supply
- 24 V DC
- Output options
- 4–20 mA, RS485 Modbus RTU and two relays standard; HART 7 and 4G optional
- Sensitivity
- Five levels, configurable by remote control
- Operating humidity
- ≤95% RH, non-condensing
- Explosion marking
- Ex d IIC T6 / DIP A20 TA,T6